Clearing Serial Port Statistics; Configuring A Serial Port - Siemens RUGGEDCOM ROX II User Manual

Cli
Hide thumbs Also See for RUGGEDCOM ROX II:
Table of Contents

Advertisement

RUGGEDCOM ROX II
CLI User Guide
show interfaces serial dnp-device-table
A table or list similar to the following appears:
ruggedcom# show interfaces serial dnp-device-table | tab
DEVICE
ADDRESS
REMOTE IP
---------------------------------
10
-
20
10.200.22.199
This table or list provides the following information:
Parameter
device-address
remote-ip
serial-port
Section 3.19.5

Clearing Serial Port Statistics

To clear the statistics collected for a specific serial port, type:
interfaces serial port name clear-port-stats
Where:
• name is the name assigned to the port
Section 3.19.6

Configuring a Serial Port

To configure a serial port, do the following:
IMPORTANT!
Do not enable flow control when Modbus TCP protocol is enabled.
1.
Make sure the CLI is in Configuration mode.
2.
Navigate to interface » serial » {port}, where {port} is the serial port.
3.
Configure the following parameter(s) as required:
Parameter
enabled
Clearing Serial Port Statistics
SERIAL
PORT
ser-3-1
-
Description
Synopsis: A string 1 to 32 characters long
The DNP device address.
Synopsis: A string 1 to 32 characters long
The IP address of the remote host that provides a connection to the this DNP device
address.
Synopsis: A string 1 to 128 characters long
The target serial port.
Description
Synopsis: true or false
Default: true
Chapter 3
Device Management
109