System Operation
9.2.3 Using the Menus
To move through the menus: Use up and down arrows to move through the options in a Menu. Use the left arrow key to move to a previous menu.
To select an option:

9.3 Basic Operation

9.3.1 Setting Time and Date
NOTE: The panel's time is as accurate as the input AC power line frequency and may drift over time if the frequency fluctuates.
1.
From the main menu, select 4 to access the Set Date and Time menu.
2.
Make changes in the fields on the screen. Use the right arrow key to move through the fields. Use the up or down arrow key to make
selections.
3.
When the date and time are correct, press ENTER.
9.3.2 Disable / Enable a Point
1.
From the main menu, select 2 for Point Functions.
2.
Select 1 for Disable/Enable Point.
Disable / Enable NACs by Template
1.
Press 1 to Disable NACs by Template or press 2 to Enable NACs by Template.
2.
Use the up or down arrow key to move through the list of templates. Press ENTER to select the current template.
Disable / Enable NACs by Group
1.
Press 3 to Disable NACs by group or press 4 to Enable NACs by group.
2.
Use the up or down arrow key to move through the list of groups. Press ENTER to select the highlighted group.
Disable / Enable Zone Points
1.
Press 5 to Disable Zone Points or press 6 to Enable Zone Points.
2.
Use the up or down arrow key to move through the list of zones. Press ENTER to select the highlighted zone.
Disable / Enable Point
1.
Press 7 to Disable/Enable Point.
2.
Select the module.
3.
Use the up or down arrow key to choose the point and press ENTER.
4.
Press the right arrow to disable or enable the point.
Inhibit Output Group
Inhibiting an output group prevents the group from being used by system mapping. While inhibited, no event in the system can activate the
output group.
1.
Press 8 to Inhibit Output Group (OPG).
2.
Use the up or down arrow key to select the desired group.
3.
Press the right arrow key to inhibit the group.
4.
Press the right arrow key again to enable the group.
9.3.3 View Event History
Use the View Event History feature to display events on LCD. From the main menu, press 3 to select the Event History. Events will begin
displaying with the most recent events appearing first.
The panel can store up to 1000 events. When it reaches its 1000 event capacity, it will delete the oldest events to make room for the new
events as they occur. In networked setups, each panel stores up to 1000 of its own events. When you view the Event History in the panel, the
most recent (newest) 500 events from every panel in the site will be displayed. When using HFSS Software Suite, all 1000 events from every
panel in the network will be uploaded.
On multi-site displays, pressing ENTER or the right arrow key brings you directly into View Event History and allows you to view the Event
History from every panel in each of the sites that the multi-site display is assigned to.
Clear Event History
From the Installer Menu select 1 for System Tests. From the Test menu, select 6 Clear History Buffer. In networked systems, this clears the
History Buffer of all panels in the site.
98
Enter the number of the option, OR press ENTER if the option appears at the top of the Menu (= symbol displays after
the option number in this case).
Table 9.3 Using the Menus
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Basic Operation