7.1 Description

The FCM-1 module is an addressable module that can be used for monitoring and switching 24 VDC Notification Appliance Circuit
(NAC) power for NFPA Class B and NFPA Class A circuits.
The FCM-1-REL is an addressable module used to switch an external power supply to a solenoid. The FCM-1-REL can be configured
for NFPA Class B or Class A wiring. When using the FCM-1-REL for Class B applications, remove jumper J1 on the back. Refer to
Figure 7.2. (For use with NFS2-3030, NFS2-640, NFS-320(C), and NFS-320SYS.)
Refer to the Device Compatibility Document for a list of compatible UL Listed Fire Alarm Releasing Solenoids. For more information
on the module specifications refer to the Installation Instructions provided with these devices.
For Class A power-supervision requirements, refer to Appendix A.2, "Supervising 24 VDC Power", on page 66.
7.1.1 Setting an SLC Address
Each module is factory preset with an address of "00." To set an SLC address refer to "Setting an SLC Address for a Module" on
page 38.

7.2 Wiring a NAC with Addressable Control Modules

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each FCM-1 module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address.
Figure 7.1 shows the connections to wire the FCM-1 module for powering a 24 VDC NAC
To remove jumper J1 from the back of the control module, follow the instructions below.
NOTE: When using NFS2-3030/NFS-3030 and the "Control" type ID, do not remove jumper J1.
Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021

Section 7: Control Modules

24 VDC Nonresettable Power (–)
24 VDC Nonresettable Power (+)
Class A NAC (+)
Class A NAC (-)
Class B/A NAC (-)
Class B/A NAC (+)
Figure 7.1 FCM-1 Wiring Connections
Rear View
Figure 7.2 FCM-1 Jumper Location
SLC (–)
SLC (+)
Jumper J1 must be removed when using the FCM-1 to
supervise 24 VDC NAC power using the no-relay
alternative wiring (see Appendix A.2.3, "Using the
Addressable Control Module Without Relay").
To remove J1 from the FCM-1:
1.
Insert a small prying tool, such
as a screwdriver or probe,
behind J1.
2.
Using the tip of the prying tool,
slide J1 toward the rear of the
FCM-1 module so that it exits
from the slot in the back.
J
P
44