Appendix 5
This section explains the time required for processing respective functions when a user program using bus interface
function, MELSEC data link function, and/or C Controller module dedicated function is executed with the task priority
set to 100.
Function specifications can be checked by using the following functions in Setting/monitoring tools for the C Controller
module.
[Help]  [Function help]  [C Controller module function help]
For the processing time of Q12DCCPU-V (Extended mode), refer to the following manual.
C Controller Module User's Manual (Hardware Design, Function Explanation)
Processing time for the bus interface functions, MELSEC data link functions, C Controller module vary somewhat depending
on the operation conditions of the OS, execution condition of the user program
The access time data shown in below are typical processing time values for respective functions
(1) Bus interface function processing time
(a) I/O access time
When accessing an input module QX42 (Start input number: X0) in a single CPU system
Function
QBF_X_In_BitEx
QBF_X_In_WordEx
When accessing an output module QY42P (Start output number: Y0) in a single CPU system
Function
QBF_Y_Out_BitEx
QBF_Y_Out_WordEx
Function Processing Time
Access size
1bit
1word
16words
64words
Access size
1bit
1word
16words
64words
Access time
µs
384
µs
428
µs
446
µs
533
Access time
µs
380
µs
413
µs
434
µs
519