(6) Command list
The commands listed in the following table can be executed in the SLMP (MC protocol) communication function
on C Controller module.
Function
Bit unit
Batch
read
Word
unit
Bit unit
Batch
write
Word
unit
Device
memory
Random
Word
read
unit
Bit unit
Test
(random
Word
write)
unit
*1 :
QnA-compatible 3E frame command
*2 :
Set the processing points within the range of the following calculation formula.
(Word access points) x 12 + (Double word access points) x 14 <= 1920
• For bit devices, 1 point is 16 bits for word access and 32 bits for double word access.
• For word devices, 1 point is 1 word for word access and 2 words for double word access.
(7) Available devices
I/O device
Internal user device
Internal system device
*1 :
ASCII code cannot be used.
Command
*1
(Subcommand)
0401
Reads bit devices in 1-point unit.
(0001)
Reads bit devices in 16-point unit.
0401
(0000)
Reads word devices in 1-point unit.
1401
Writes bit devices in 1-point unit.
(0001)
Writes bit devices in 16-point unit.
1401
(0000)
Writes word devices in 1-point unit.
Reads bit devices in 16-point unit and 32-point unit by
specifying devices and device numbers randomly.
0403
(0000)
Reads word devices in 1-point unit and 2-point unit by
specifying devices and device numbers randomly.
1402
Sets/resets bit devices in 1-point unit by specifying devices
(0001)
and device numbers randomly.
Sets/resets bit devices in 16-point unit and 32-point unit by
specifying devices and device numbers randomly.
1402
(0000)
Writes word devices in 1-point unit and 2-point unit by
specifying devices and device numbers randomly.
Device
Device
code
Input
9C
H
Output
9D
H
Internal relay
90
H
Data register
A8
H
Link relay
A0
H
Link register
B4
H
Special relay
91
H
Special register
A9
H
CHAPTER 12 FUNCTIONS ACCESSED VIA ETHERNET PORTS
Description
Device number range
*1
0
to FFF
H
H
0
to FFF
H
H
The range can be specified with the device
numbers available on the target C Controller
module.
0 to 2047
0 to 2047
Processing
points
7168 points
960 words
12
(15360 points)
960 points
7168 points
960 words
(15360 points)
960 points
192 points
188 points
*2
Hexadecimal
Hexadecimal
Decimal
Decimal
Hexadecimal
Hexadecimal
Decimal
Decimal
207