Error
Error message
code
information
Refresh cycle
(set value: ms)/
5012
REF. TIME OVER
7000
MULTI CPU DOWN
Module No.
7002
MULTI CPU DOWN
Module No.
7010
MULTI EXE.ERROR
Module No.
Module No.
7011
MULTI EXE.ERROR
Module No.
7013
MULTI EXE.ERROR
Module No.
418
LED status
Error
RUN
ERR.
Refresh time
On
On
(measured
value: ms)
*1
Off
Flashing
*1
Off
Flashing
*1
Off
Flashing
*1
Off
Flashing
*1
Off
Flashing
*1
Off
Flashing
CPU
operation
Error details and cause
status
The sum of the data refresh time and link
refresh time exceeds the set refresh cycle.
• The refresh cycle value is too short.
• The number of set refresh points is
excessive.
• A task of high CPU utilization is running.
(Ethernet communication load is high,
etc.)
Continue
The C Controller module was restarted
while online connection with CW
*5
Workbench.
For precautions for program debugging,
refer to the following.
 Setting/Monitoring Tools for the C
Controller Module Version 4 Operating
Manual
• In the operating mode of the multiple
CPU system, a CPU error occurred in the
CPU for which "All station stop by stop
error of CPU" is selected.
• In the multiple CPU system, a CPU
module incompatible with the multiple
CPU system is mounted.
• When CPU No.1 is a Basic model QCPU,
a "CPU (Empty)" slot is set on the right
Stop
side of the C Controller module.
• Any CPU module other than CPU No.1
was disconnected from the base unit
during operation. Or any CPU module
other than CPU No.1 was reset.
In the multiple CPU system, a stop error
occurred in CPU No.1 during power-on, and
thereby the other CPUs (No.2 to No.4)
cannot start.
• During the initial communication in the
multiple CPU system, no response
returns from the target CPU.
Stop
• In the multiple CPU system, a CPU
module incompatible with the multiple
CPU system is mounted.
• In the multiple CPU system, a faulty CPU
module is mounted.
• In the multiple CPU system, a CPU
module incompatible with the multiple
CPU system is mounted. (A CPU module
Stop
compatible with the multiple CPU system
detects this error.)
• In the multiple CPU system, any of the
CPU No.2 to No.4 was reset with power
ON. (A CPU that released from the reset
status detects this error.)
In a multiple CPU system, the either of
following setting was set.
• Set the multiple CPU auto refresh setting
to the CPU module that cannot execute
Stop
the multiple CPU auto refresh setting.
• Set the I/O sharing when using Multiple
CPUs to the CPU module that cannot
read the I/O of outside of the group.
It does not meet the system requirement to
use the multiple CPU high speed
transmission.
• It is not used QnUD(H)CPU or
QnDCCPU in CPU No.1.
• It is not used the multiple CPU high
speed main base unit (Q3DB).
Stop
• The send range is set excluding 0 point
to the CPU module that is not supported
the multiple CPU high speed
transmission.
• The send range is set excluding 0 point
to the CPU module that is not supported
the multiple CPU interchangeability area.
Q172(H)CPU(N) or Q173(H)CPU(N) is
Stop
installed in CPU slot and slot 0 to 2 (There is
a possibility that the module breaks down.).
Corrective action
• Increase the refresh cycle value in
Setting/monitoring tools for the C
Controller module.
• Decrease the number of set refresh
points in Setting/monitoring tools for the
C Controller module.
• Decrease the CPU utilization of the task,
or disable the task operation.
Restart the C Controller module with CW
*5
Workbench connection disconnected.
• Identify the error of the CPU module and
eliminate the error cause.
• Remove the incompatible CPU module
from the main base unit.
• Change the setting.
• Check the mounting status of CPU
modules other than CPU No.1 and
whether the CPU modules were reset.
Identify the error of the CPU module and
eliminate the error cause.
• Remove the incompatible CPU module
from the main base unit.
• Replace the incompatible CPU module
with a compatible one.
• Reset the CPU module and restart it.
• If the same error is displayed again,
check the modules and replace a faulty
module.
• Replace the faulty CPU.
• Replace it with a CPU module that is
compatible with the multiple CPU
system.
• Do not reset any of CPU No.2 to No.4.
• Reset CPU No.1 and restart the multiple
CPU system.
• Correct the multiple CPU automatic
refresh setting.
• Correct the "I/O sharing when using
multiple CPUs" setting.
• Change the system configuration so that
the conditions for using the multiple CPU
high speed transmission function are
met.
• When performing automatic refresh in
the multiple CPU compatible area, set
the send range of a CPU that does not
support the function to zero points.
Check QCPUs and Motion CPUs that can
be used in multiple CPU systems, and
change the system configuration.