(7) Actions against each event No. that occurs in "MCFDrv"
Actions against each event No. that occurs in "MCFDrv" are described below.
Event No.
Event type
C0000480
System (Err.)
CF card is not responding.
H
C0000481
System (Err.)
An error occurred during acquiring the CF card information.
H
C0000482
System (Err.)
An error occurred during reading master boot record (MBR).
H
C0000483
System (Err.)
The master boot record (MBR) cannot be recognizes in this format.
H
C0000490
System (Err.)
A resource shortage error occurred.
H
C0000491
System (Err.)
A CF card driver initialization error occurred.
H
C0000493
System (Err.)
A block number error occurred.
H
(8) Actions against each event No. that occurs in "MEtherDrv"
There is no event that may occur in "MEtherDrv".
(9) Actions against each event No. that occurs in "MRs232Drv"
There is no event that may occur in "MRs232Drv".
(10)Actions against each event No. that occurs in "MUSBDrv"
Actions against each event No. that occurs in "MUSBDrv" are described below.
Event No.
Event type
An external device where current exceeding allowable supply current
80000000
System (Warning)
H
flows was connected.
(11)Actions against each event No. that occurs in "MelsecIF"
Actions against each event No. that occurs in "MelsecIF" are described below.
Event No.
Event type
40000004
System (Info.)
User CPU restart was executed.
H
C0000000
System (Err.)
MAIN CPU DOWN occurred.
H
C0000001
System (Err.)
PARAMETER ERROR occurred.
H
C0000002
System (Err.)
SP.UNIT ERROR occurred.
H
C0000003
System (Err.)
REF.TIME OVER occurred.
H
C0001000
System (Err.)
MAIN CPU DOWN occurred.
H
C0001001
System (Err.)
A battery backup RAM error was detected.
H
Event
• Pull the CompactFlash card once, and insert it again.
• Replace the CompactFlash card.
• Pull the CompactFlash card once, and insert it again.
• Reformat the CompactFlash card on a personal computer, etc.
• Replace the CompactFlash card.
• Reformat the CompactFlash card on a personal computer, etc.
• Replace the CompactFlash card.
Check the memory usage condition, and execute again after creating
a free capacity of the memory.
Please consult your local Mitsubishi service center or representative,
explaining the details of the problem.
Event
Check the current consumption of the external device and review the
configuration so that it is below the allowable supply current of the C
Controller module.
Event
Refer to the CPU error code 1000.
Refer to the CPU error code 3001.
Refer to the CPU error code 2110.
Refer to the CPU error code 5012.
Refer to the CPU error code 1000.
Refer to the CPU error code 1106.
APPENDICES
Corrective action
Corrective action
Corrective action
-