4.2

Trip matrix logic TMAGAPC

4.2.1

Identification

Function description
Trip matrix logic
4.2.2

Application

The trip matrix logic (TMAGAPC) function is used to route trip signals and other logical output
signals to different output contacts on the IED.
The trip matrix logic function has 3 output signals and these outputs can be connected to
physical tripping outputs according to the specific application needs for settable pulse or
steady output.
4.2.3

Setting guidelines

Operation : Operation of function On / Off .
PulseTime : Defines the pulse time when in Pulsed mode. When used for direct tripping of
circuit breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order to
obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
OnDelay : Used to prevent output signals to be given for spurious inputs. Normally set to 0 or a
low value.
OffDelay : Defines a delay of the reset of the outputs after the activation conditions no longer
are fulfilled. It is only used in
the off delay time shall be set to at least 0.150 seconds in order to obtain a satisfactory
minimum duration of the trip pulse to the circuit breaker trip coils.
ModeOutputx : Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed .
4.3

Logic for group alarm ALMCALH

4.3.1
Identification
Function description
Logic for group alarm
4.3.2
Application
Group alarm logic function ALMCALH is used to route alarm signals to different LEDs and/or
output contacts on the IED.
Switchgear control unit SAM600-IO
Application manual
IEC 61850
identification
TMAGAPC
Steady mode. When used for direct tripping of circuit breaker(s)
IEC 61850
identification
ALMCALH
© Copyright 2017 ABB. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-70B268A9-B248-422D-9896-89FECFF80B75 v1
Section 4
Logic
IP15121-1 v4
SEMOD167882-2 v3
M15321-3 v13
M15291-3 v5
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion sam600-io

Table of Contents