Mains Power Distribution - Honeywell MAXPRO-Net Hardware Installation Manual

Crosspoint matrix video switching system
Hide thumbs Also See for MAXPRO-Net:
Table of Contents

Advertisement

9.6.1

Mains Power Distribution

Mains Supply Power distribution is equally important and raises a second concern for
ELECTRICAL SAFETY. In most countries, the power utilities company will state that any
power circuit must deliver a minimum current capacity of 10amps (13amps in some
countries) at a switched GPO outlet. The safety and work practice standards in your
country for mains power distribution must be observed at all times.
The following table should be used as a guide only to help understand how power
distribution requirements affect the minimum conductor diameter size.
Max Load
Max Distance
50m
100m
150m
200m
300m
400m
500m
600m
Rev. C
Supply = 240v AC @ 5%
1 Amp
2 Amps
1.0mm²
1.0mm²
1.0mm²
1.0mm²
1.0mm²
1.5mm²
1.0mm²
1.5mm²
1.5mm²
2.5mm²
1.5mm²
4.0mm²
1.5mm²
4.0mm²
2.5mm²
6.0mm²
9-10
4 Amp
6 Amp
1.0mm²
1.5mm²
1.5mm²
2.5mm²
2.5mm²
4.0mm²
4.0mm²
6.0mm²
6.0mm²
-
6.0mm²
-
-
-
-
-
8 Amp
10 Amp
1.5mm²
2.5mm²
4.0mm²
4.0mm²
6.0mm²
6.0mm²
6.0mm²
10mm²
-
-
-
-
-
-
-
-