9.6 POWER DISTRIBUTION, CONTINUED
Below are three tables aimed to help with the estimation of conductor diameters
required. The variables are stated as follows:
9. 1. DISTANCE required in Meters.
10. 2. MAXIMUM LOAD current in Amps.
11. 3. MINIMUM CONDUCTOR diameter in Square Millimeters (mm², surface area).
12.
Max Load
Max Distance
50m
75m
100m
150m
200m
250m
300m
350m
400m
450m
500m
Rev. C
Supply = 24v AC @ 10%
2.0 Amps
2.5mm²
4.0mm²
4.0mm²
6.0mm²
10mm²
10mm²
-
-
-
-
-
Supply = 24v AC @ 10%
4.0 Amps
Max Load
Max Distance
5m
1.0mm²
10m
1.0mm²
15m
1.5mm²
20m
1.5mm²
30m
2.5mm²
1.5 Amps
1.0 Amps
1.0mm²
1.0mm²
2.5mm²
1.5mm²
2.5mm²
2.5mm²
6.0mm²
4.0mm²
6.0mm²
4.0mm²
10mm²
6.0mm²
10mm²
6.0mm²
10mm²
10mm²
-
10mm²
-
10mm²
-
10mm²
8.0 Amps
1.0mm²
1.5mm²
2.5mm²
4.0mm²
6.0mm²
9-9
0.5 Amps
1.0mm²
1.0mm²
1.0mm²
1.5mm²
2.5mm²
4.0mm²
4.0mm²
4.0mm²
4.0mm²
6.0mm²
6.0mm²
HMXMU001018
10/06