9.8 SUBRACK CURRENT CONSUMPTION, CONTINUED
Rev. C
NOTE: Total subrack's current consumption is
calculated with the subrack fully populated with RD85,
RD200 and RD430 modules, where applicable. Whatever
warning needed.
CAUTION: The stated current consumption for subracks
using I/O modules is based on using RD400 and RD430
modules. When using RD440 relay output modules, an
addition 250mA (per RD440 module) must be added to
the subrack total current consumption.
CAUTION: Where an RD200 is indicated, RD205 and
RD220 may be used. (Add 35mA/RD205module and
70mA/RD220 to subrack current shown) Whatever
warning needed.
9-13
HMXMU001018
10/06