7.15.3

Connector Details

All connections to the RD490 module are via the male DB25 connector located on the
rear panel of the I/O subrack for the slot position being used. It can be wired for PPM
Infrared control (of eight devices) or RS-232 control of one device.
D25 CONNECTOR
Rev. C
FUNCTION
1
RS-232 Receive Data
2
RS-232 Transmit Data
3
Common Ground
4
Common Ground
5
PPM output 1
6
PPM output 2
7
PPM output 3
8
PPM output 4
9
PPM output 5
10
PPM output 6
11
PPM output 7
12
PPM output 8
13
Common Ground
14
RS-232 Ground
15
RS-232 Ground
16
+9V out
17
+5V out
18
Sense input 1
19
Sense input 2
20
Sense input 3
21
Sense input 4
22
Sense input 5
23
Sense input 6
24
Sense input 7
25
Sense input 8
7.15-2