Application

A circuit breaker is used to connect two different power networks. It is essential to
ensure that these power networks are synchronized before closing the circuit breaker,
otherwise it may lead to disturbances in the power system, causing stress and damage
to the connected equipment.
ASGCSYN controls the closing of the generator circuit breakers in power networks;
it enables the closing after matching the voltage and frequency conditions to achieve
synchronism. ASGCSYN also participates in matching voltage and frequency
conditions for the network breaker synchronization.
ASGCSYN includes both the synchronization check function and the energizing
function to allow closing when one side of the breaker is dead.
The participation of ASGCSYN in matching of voltage and frequency conditions for
the network breaker synchronization is described via one of the typical application
example as shown in
Figure
Source
2
ASGCSYN
(SCB2)
ASCGAPC
ASNSCSYN
(NSCB1)
ASCGAPC
GUID-85BFFDEF-69C3-4E53-9143-95CE4B074E34 V1 EN
Figure 764:
ASGCSYN participation in matching of V, F during network breaker
synchronization
764.
Source
1
ASGCSYN
(SCB1)
ASCGAPC
Bus1
Start
Matching
ASNSCSYN
∆U, ∆F
(NSCB2)
ASCGAPC
1MRS759142 C
(Equation 330)
ASNSCSYN
(NSCB3)
ASCGAPC
Bus2
Synchronize