Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 9
Control functions
9.5.9
9.5.10
1398

Monitored data

Table 1351:
SECRSYN Monitored data
Name
Type
ENERG_STATE
Enum
U_DIFF_MEAS
FLOAT32
FR_DIFF_MEAS
FLOAT32
PH_DIFF_MEAS
FLOAT32
U_DIFF_SYNC
BOOLEAN
PH_DIF_SYNC
BOOLEAN
FR_DIFF_SYNC
BOOLEAN
SECRSYN
Enum
Technical data
Table 1352:
SECRSYN Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Operate time accuracy in definite time mode
Values (Range)
Unit
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
-3.00...3.00
xUn
-1.500...1.500
xFn
-180.00...180.00
deg
0=False
1=True
0=False
1=True
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the voltage
measured: f
±1 Hz
n
Voltage:
±3.0% of the set value or ±0.01 × U
Frequency:
±10 mHz
Phase angle:
±3°
<50 ms
Typically 0.96
±1.0% of the set value or ±20 ms
1MRS759142 C
Description
Energization state of Line
and Bus
Calculated voltage
amplitude difference
Calculated voltage
frequency difference
Calculated voltage phase
angle difference
Voltage difference out of
limit for synchronizing
Phase angle difference
out of limit for
synchronizing
Frequency difference out
of limit for synchronizing
Status
n
REX640