Section 9
Control functions
9.7.7
1444
Voltage angle difference adjustment
In applications where the power transformer is located between the voltage
measurement and the CB, the vector group connection gives phase difference to the
voltages between the high- and low-voltage sides. The angle adjustment can be used
to meet synchronism.
The vector group of the power transformer is defined with clock numbers, where the
value of the hour pointer defines the low-voltage-side phasor and the high-voltage-
side phasor is always fixed to the clock number 12, which is the same as zero. The
angle between clock numbers is 30°. When comparing phase angles, the U_BUS_A
input is always the reference. This means that when the Yd11 power transformer is
used, the low-voltage-side voltage phasor leads the high-voltage-side phasor by 30º or
lags by 330º. The rotation of the phasors is counterclockwise.
The generic rule is that a low-voltage-side phasor lags the high-voltage-side phasor by
clock number ⋅ 30º. This is called angle difference adjustment and can be set for
ASNSCSYN with the Phase shift setting.

Signals

Table 1373:
ASNSCSYN Input signals
Name
Type
U3P1
SIGNAL
U3P2
SIGNAL
BLOCK
BOOLEAN
BYPASS
BOOLEAN
CL_COMMAND
BOOLEAN
EXT_CHECK
BOOLEAN
CB_TEST
BOOLEAN
CB_OPEN
BOOLEAN
CB_CLOSE
BOOLEAN
ISO_A1_CLOSE
BOOLEAN
ISO_B1_CLOSE
BOOLEAN
ISO_A2_CLOSE
BOOLEAN
ISO_B2_CLOSE
BOOLEAN
ASC1_NS_DAT
INT32
Table 1374:
ASNSCSYN Output signals
Name
Type
CL_FAIL_AL
BOOLEAN
CMD_FAIL_AL
BOOLEAN
AS_INIT_FAIL
BOOLEAN
Table continues on next page
Default
Description
-
Three-phase voltages (Bus B side)
-
Three-phase voltages (Bus A side)
0=False
Blocking signal of the auto synchronization function
0=False
Bypass for synchronization and closing conditions
check
0=False
External closing request
0=False
External permissive check for CB close
0=False
Circuit breaker test position status
0=False
Circuit breaker open status
0=False
Circuit breaker close status
0=False
Isolator A1 close status
0=False
Isolator B1 close status
0=False
Isolator A2 close status
0=False
Isolator B2 close status
0
Coded integer data from ASCGAPC1
Description
CB closing failed
CB closing request failed
Synchronization not initiated
1MRS759142 C
REX640
Technical Manual