Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.7.8
Table 1375:
ASNSCSYN Group settings (Basic)
Parameter
Values (Range)
Live dead mode
Diff voltage
Diff frequency
Diff angle
Table 1376:
ASNSCSYN Group settings (Advanced)
Parameter
Values (Range)
Multiple command
Voltage offset
Frequency offset
REX640
Technical Manual
Name
CLOSE_CB
SYNC_OK
MATCH_OK
MATCH_INPRO
SYNC_INPRO
LADB
LALB
DALB
DADB
U_DIFF
FR_DIFF_MEAS
CB_SELECTED
NS_ASC_DAT

Settings

Unit
-2=Command
-1=Off
1=Both Dead
2=Live B, Dead A
3=Dead B, Live A
4=Dead A, B Any
5=Dead B, A Any
6=One Live, Dead
7=Not Both Live
0.01...0.50
xUn
0.001...0.060
xFn
5...90
deg
Unit
0=Off
1=On
-0.100...0.100
xUn
-0.010...0.010
xFn
Type
Description
BOOLEAN
CB close signal
BOOLEAN
Systems in synchronism
BOOLEAN
Voltage and frequency of the systems matched
BOOLEAN
Voltage and frequency matching in progress
BOOLEAN
Synchronization in progress
BOOLEAN
Live bus A, dead bus B
BOOLEAN
Live bus A, live bus B
BOOLEAN
Dead bus A, live bus B
BOOLEAN
Dead bus A, dead bus B
FLOAT32
Line voltage difference across synchronizing CB
FLOAT32
Calculated voltage frequency difference
BOOLEAN
CB selected for synchronization
INT32
Integer weighted output data to ASCGAPC
Step
Default
1=Both Dead
0.01
0.05
0.001
0.001
1
5
Step
Default
0=Off
0.001
0.000
0.001
0.000
Section 9
Control functions
Description
Live dead mode
Maximum voltage difference limit
Maximum frequency difference limit
Maximum angle difference limit
Description
Multiple command to the circuit breaker
Voltage offset
Frequency offset
1445