1MRS759142 C
9.9.6.3
REX640
Technical Manual

Configuration examples

PHHPTOC
I _A
OPERATE
I _B
START
I _C
BLOCK
ENA _MULT
PHLPTOC
OPERATE
I_ A
I_ B
START
I_ C
BLOCK
ENA_ MULT
EFLPTOC
Io
OPERATE
BLOCK
START
ENA_ MULT
Circuit breaker position
information from binary input
Conditions to verify if circuit breaker
is ready to be reclosed
GUID-2604652C-B689-417D-AAC4-0115531510E3 V1 EN
Figure 804:
Example connection between protection and autoreclosing functions
in protection relay configuration
It is possible to create several sequences for a configuration.
Autoreclose sequences for overcurrent and non-directional earth-fault protection
applications where high speed and delayed autoreclosings are needed can be as
follows:
Example 1
The sequence is implemented by two shots which have the same reclosing time for all
protection functions, namely I>>, I> and Io>. The initiation of the shots is done by
activating the operating signals of the protection functions.
Control functions
DARREC
INIT _1
OPEN _CB
INIT _2
CLOSE _CB
CMD_W AIT
INIT _3
INIT _4
INPRO
LOCKED
INIT _5
PROT_ CRD
INIT _6
UNSUC_ RECL
DEL _INIT _2
DEL _INIT _3
AR_ON
DEL _INIT _4
READY
BLK _RECL_ T
BLK _RCLM_T
BLK _THERM
CB _POS
CB _READY
INC_ SHOTP
INHIBIT _RECL
RECL _ON
SYNC
Section 9
OR
CB_ TRIP
CB_CLOSE
1527