Fast Trip In Switch On To Fault - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 9
Control functions
9.9.6.6
1532
optimal solution. Using protection start signals instead of protection trips for initiating
shots shortens the trip times.
Example 1
When a two-shot-sequence is used, the start information from the protection function
is routed to the DEL_INIT 2 input and the operate information to the INIT_2 input.
The following conditions have to apply:
protection operate time = 0.5s
Str 2 delay shot 1 = 0.05s
Str 2 delay shot 2 = 60s
Str 2 delay shot 3 = 60s
Operation in a permanent fault:
1.
Protection starts and activates the DEL_INIT 2 input.
2.
After 0.05 seconds, the first autoreclose shot is initiated. The function opens the
circuit breaker: the OPEN_CB output activates. The total trip time is the
protection start delay + 0.05 seconds + the time it takes to open the circuit breaker.
3.
After the first shot, the circuit breaker is reclosed and the protection starts again.
4.
Because the delay of the second shot is 60 seconds, the protection is faster and
trips after the set operation time, activating the INIT 2 input. The second shot
is initiated.
5.
After the second shot, the circuit breaker is reclosed and the protection starts
again.
6.
Because the delay of the second shot is 60 seconds, the protection is faster and
trips after the set operation time. No further shots are programmed after the final
trip. The function is in lockout and the sequence is considered unsuccessful.
Example 2
The delays can be used also for fast final trip. The conditions are the same as in
Example 1, with the exception of Str 2 delay shot 3 = 0.10 seconds.
The operation in a permanent fault is the same as in Example 1, except that after the
second shot when the protection starts again, Str 2 delay shot 3 elapses before the
protection operate time and the final trip follows. The total trip time is the protection
start delay + 0.10 seconds + the time it takes to open the circuit breaker.

Fast trip in Switch on to fault

The Str _ delay shot 4 parameter delays can also be used to achieve a fast and
accelerated trip with SOTF. This is done by setting the Fourth delay in SOTF
parameter to "1" and connecting the protection start information to the corresponding
DEL_INIT_ input.
When the function detects a closing of the circuit breaker, that is, any other closing
except the reclosing done by the function itself, it always prohibits shot initiation for
1MRS759142 C
REX640
Technical Manual