Fitting
The procedure below details how to fit the units.
1
2
3
4
24 V power supply
I/O units are supplied with 24 V power from the connector XT31 (see previous
illustration).
Parallel connection
The 24V coming from DSQC 662, terminal XT31.1, can not be increased by adding
power from any other 24 V power supply (not even DSQC 609). There is no load
levelling function that ensures current distribution. The unit will not be destroyed
but the lifetime may be affected.
The parallel connection of two DSQC 609 is permitted (factory setting) but not more
than two.
Product manual - IRC5
3HAC047136-001 Revision: M
2.9.4 Installation of DeviceNet I/O, Gateways and encoder interface units, IRC5
Action
DANGER
Before commencing any work inside the
cabinet, please observe the safety inform-
ation in section
Make sure that the main
power has been switched off on page
Fit the DeviceNetI/O unit by snapping it
onto the mounting rail.
Connect the DC supply to the board.
Connect wires to the inputs and output
connectors as required.
© Copyright 2004-2018 ABB. All rights reserved.
2 Installation and commissioning
Note/Illustration
26.
Described in the Application manual for
the respective busses.