Alarm Messages Generated By The Drive - ABB ACS355 series User Manual

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

Alarm messages generated by the drive

CODE ALARM
2001
OVERCURRENT
0308
bit 0
(programmable fault
function 1610)
2002
OVERVOLTAGE
0308
bit 1
(programmable fault
function 1610)
2003
UNDERVOLTAGE
0308
bit 2
2004
DIR LOCK
0308
bit 3
2005
IO COMM
0308
bit 4
(programmable fault
function 3018, 3019)
2006
AI1 LOSS
0308
bit 5
(programmable fault
function 3001, 3021)
2007
AI2 LOSS
0308
bit 6
(programmable fault
function 3001, 3022)
2008
PANEL LOSS
0308
bit 7
(programmable fault
function 3002)
2009
DEVICE
OVERTEMP
0308
bit 8
CAUSE
Output current limit
controller is active.
High ambient
temperature.
DC overvoltage
controller is active.
DC undervoltage
controller is active.
Change of direction is
not allowed.
Fieldbus
communication break
Analog input AI1 signal
has fallen below limit
defined by parameter
3021 AI1 FAULT
LIMIT.
Analog input AI2 signal
has fallen below limit
defined by parameter
3022 AI2 FAULT
LIMIT.
Control panel selected
as active control
location for drive has
ceased
communicating.
Drive IGBT
temperature is
excessive. Alarm limit
depends on the drive
type and size.
Fault tracing 351
WHAT TO DO
Check ambient conditions. Load
capacity decreases if installation site
ambient temperature exceeds 40 °C
(104 °F). See section
page 376.
For more information, see fault
in
Fault messages generated by the
drive
on page 357.
For more information, see fault
in
Fault messages generated by the
drive
on page 357.
For more information, see fault
in
Fault messages generated by the
drive
on page 351.
Check parameter
1003 DIRECTION
settings.
Check status of fieldbus
communication. See chapter
control with embedded fieldbus
page 313, chapter
Fieldbus control
with fieldbus adapter
appropriate fieldbus adapter manual.
Check fault function parameter
settings.
Check connections.
Check if master can communicate.
For more information, see fault
in
Fault messages generated by the
drive
on page 357.
For more information, see fault in
0008 Fault messages generated by
the drive
on page 357.
For more information, see fault
in
Fault messages generated by the
drive
on page 357.
Check ambient conditions. See also
section
Derating
on page 376.
Check air flow and fan operation.
Check motor power against drive
power.
Derating
on
0001
0002
0003
Fieldbus
on
on page
339
or
0007
0010

Hide quick links: