All parameters
No.
Name/Value
DI4(INV)
DI5(INV)
1607 PARAM SAVE
DONE
SAVE...
1608 START
ENABLE 1
NOT SEL
DI1
Description
See selection DI1(INV).
See selection DI1(INV).
Saves the valid parameter values to the permanent
memory.
Note: A new parameter value of a standard macro is saved
automatically when changed from the panel but not when
altered through a fieldbus connection.
Saving completed
Saving in progress
Selects the source for the Start enable 1 signal.
Note: Functionality of the Start enable signal is different
from the Run enable signal.
Example: External damper control application using Start
enable and Run enable. Motor can start only after the
damper is fully open.
Drive started
Relay energized
Relay
de-
energized
Damper
closed
Damper
opening
time
Motor
speed
Start enable signal is on.
External signal required through digital input DI1. 1 = Start
enable. If the Start enable signal is switched off, the drive
will not start or it coasts to stop if it is running and alarm
START ENABLE 1 MISSING
The drive can also ramp to stop depending on parameter
2102 STOP
FUNCTION.
Actual signals and parameters 213
Damper open
Damper
closed
Damper
closing
time
Run enable signal
from the damper end
Acceleration
Deceleration
time (2202)
time (2203)
(2021) is activated.
Def/FbEq
-4
-5
DONE
0
1
NOT SEL
Start/Stop
command
(group 10)
Start enable
signals
(1608
and 1609)
Started
output status
(group 14)
Damper
status
switch when the
damper is fully
opened. (1601)
Motor
status
0
1