No.
Name/Value
3416 SIGNAL3 MIN
x...x
3417 SIGNAL3 MAX Defines the maximum value for the signal selected by
x...x
3418 OUTPUT3 DSP
FORM
3419 OUTPUT3
UNIT
3420 OUTPUT3 MIN Sets the minimum display value for the signal selected by
x...x
3421 OUTPUT3
MAX
x...x
35 MOTOR TEMP
MEAS
3501 SENSOR
TYPE
NONE
1 x PT100
2 x PT100
3 x PT100
Description
Defines the minimum value for the signal selected by
parameter 3415. See parameter
Setting range depends on parameter
PARAM
setting.
parameter
3415 SIGNAL3
SIGNAL1
MIN.
Setting range depends on parameter
PARAM
setting.
Defines the format for the displayed signal selected by
parameter
3415 SIGNAL3
See parameter
3404 OUTPUT1 DSP
Selects the unit for the displayed signal selected by
parameter
3415 SIGNAL3
See parameter
3405 OUTPUT1
parameter
3415 SIGNAL3
SIGNAL1
MIN.
Setting range depends on parameter
PARAM
setting.
Sets the maximum display value for the signal selected by
parameter
3415 SIGNAL3 PARAM.
SIGNAL1
MIN.
Setting range depends on parameter
Motor temperature measurement. See section
temperature measurement through the standard I/O
page 157.
Activates the motor temperature measurement function and
selects the sensor type. See also parameter group
ANALOG
OUTPUTS.
The function is inactive.
The function is active. The temperature is measured with
one Pt100 sensor. Analog output AO feeds constant current
through the sensor. The sensor resistance increases as the
motor temperature rises, as does the voltage over the
sensor. The temperature measurement function reads the
voltage through analog input AI1/2 and converts it to
degrees centigrade.
The function is active. Temperature is measured using two
Pt100 sensors. See selection
The function is active. Temperature is measured using three
Pt100 sensors. See selection
Actual signals and parameters 267
3402 SIGNAL1
3415 SIGNAL3
PARAM. See parameter
3415 SIGNAL3
PARAM.
FORM.
PARAM.
UNIT.
PARAM. See parameter
3415 SIGNAL3
See parameter
3415
setting.
Motor
1 x
PT100.
1 x
PT100.
Def/FbEq
-
MIN.
-
-
3402
-
DIRECT
-
-
-
-
3402
-
-
3402
-
on
NONE
15
0
1
2
3

Hide quick links: