ABB ACS355 series User Manual page 233

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
COMM
SEQ PROG
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
2202 ACCELER
TIME 1
0.0...1800.0 s
Description
Fieldbus interface as the source for ramp pair 1/2 selection,
ie, Control word
0301 FB CMD WORD 1
word is sent by the fieldbus controller through the fieldbus
adapter or embedded fieldbus (Modbus) to the drive. For
the Control word bits, see section
profile
on page 333.
Note: This setting applies only for the DCU profile.
Sequence programming ramp defined by parameter
ST1 RAMP
(or 8423/.../8492)
Inverted digital input DI1. 0 = ramp pair 2, 1 = ramp pair 1.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Defines the acceleration time 1, ie, the time required for the
speed to change from zero to the speed defined by
parameter
2008 MAXIMUM FREQ
MAXIMUM SPEED
(in vector control). The control mode is
selected by parameter
• If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the
acceleration rate.
• If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the
reference signal.
• If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive operating limits.
Actual acceleration time depends on parameter
SHAPE 1
setting.
Time
Actual signals and parameters 233
bit 10. The Control
DCU communication
(in scalar control) /
9904 MOTOR CTRL
Def/FbEq
7
8422
10
-1
-2
-3
-4
-5
5.0 s
2002
MODE.
2204 RAMP
1 = 0.1 s