All parameters
No.
Name/Value
5132 FBA CPI FW
REV
5133 FBA APPL FW
REV

52 PANEL COMM

5201 STATION ID
1...247
5202 BAUD RATE
1.2 kb/s
2.4 kb/s
4.8 kb/s
9.6 kb/s
19.2 kb/s
38.4 kb/s
57.6 kb/s
115.2 kb/s
5203 PARITY
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
5204 OK
MESSAGES
0...65535
Description
Displays the common program revision of the adapter
module in format axyz, where:
• a = major revision number
• xy = minor revision numbers
• z = correction letter.
Example: 190A = revision 1.90A
Common program revision of the adapter module
Displays the application program revision of the adapter
module in format axyz, where:
• a = major revision number
• xy = minor revision numbers
• z = correction letter.
Example: 190A = revision 1.90A
Application program revision of the adapter module
Communication settings for the control panel port on the
drive
Defines the address of the drive. Two units with the same
address are not allowed on-line.
Address
Defines the transfer rate of the link.
1.2 kbit/s
2.4 kbit/s
4.8 kbit/s
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
115.2 kbit/s
Defines the use of parity and stop bit(s). The same setting
must be used in all on-line stations.
8 data bits, no parity bit, one stop bit
8 data bits, no parity bit, two stop bits
8 data bits, even parity indication bit, one stop bit
8 data bits, odd parity indication bit, one stop bit
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
Number of messages
Actual signals and parameters 289
Def/FbEq
1 = 1
1 = 1
1
1 = 1
9.6 kb/s
1 =
0.1 kbit/s
8 NONE 1
0
1
2
3
0
1 = 1