Permanent magnet synchronous motor
nameplate example:
• motor nominal voltage (parameter 9905).
For permanent magnet synchronous motors, enter
the back emf voltage at nominal speed here.
Otherwise use nominal voltage and perform ID run.
If the voltage is given as voltage per rpm, eg, 60 V
per 1000 rpm, the voltage for 3000 rpm nominal
·
speed is 3
60 V = 180 V.
• nominal motor current (parameter 9906)
Allowed range: 0.2...2.0 · I
• motor nominal frequency (parameter 9907)
• motor nominal speed (parameter 9908)
• motor nominal power (parameter 9909)