278 Actual signals and parameters
All parameters
No.
Name/Value
4015 FBK
MULTIPLIER
-32.768...
32.767
4016 ACT1 INPUT
AI1
AI2
CURRENT
TORQUE
POWER
COMM ACT 1
COMM ACT 2
FREQ INPUT
4017 ACT2 INPUT
4018 ACT1
MINIMUM
-1000...1000% Value as a percentage
Description
Defines an extra multiplier for the value defined by
parameter
4014 FBK
applications where feedback value is calculated from
another variable (eg, flow from pressure difference).
Multiplier. If parameter value is set to zero, no multiplier is
used.
Defines the source for actual value 1 (ACT1). See also
parameter
4018 ACT1
Uses analog input 1 for ACT1
Uses analog input 2 for ACT1
Uses current for ACT1
Uses torque for ACT1
Uses power for ACT1
Uses value of signal
Uses value of signal
Frequency input
Defines the source for actual value ACT2. See also
parameter
4020 ACT2
See parameter
4016 ACT1
Sets the minimum value for ACT1.
Scales the source signal used as the actual value ACT1
(defined by parameter
4016
values 6
(COMM ACT
scaling is not done.
Par
Source
4016
1
Analog input 1
2
Analog input 2
3
Current
4
Torque
5
Power
A = Normal; B = Inversion (ACT1 minimum > ACT1
maximum)
ACT1 (%)
A
4019
4018
Source max.
Source min.
Source signal
SEL. Parameter is used mainly in
MINIMUM.
0158 PID COMM VALUE 1
0159 PID COMM VALUE 2
MINIMUM.
INPUT.
4016 ACT1
INPUT). For parameter
1) and 7
(COMM ACT
Source min.
1301 MINIMUM AI1
1302 MAXIMUM AI1
1304 MINIMUM AI2
1305 MAXIMUM AI2
0
2
·
-2
nominal torque
2
·
-2
nominal power
2
ACT1 (%)
4018
4019
Source min.
Source signal
Def/FbEq
0.000
1 = 0.001
AI2
1
2
3
4
5
for ACT1
6
for ACT1
7
8
AI2
0%
2)
Source max.
·
nominal current
·
nominal torque
·
nominal power
B
Source max.
1 = 1%