ABB ACS355 series User Manual page 317

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

Parameter
1106 REF2
SELECT
OUTPUT SIGNAL SOURCE SELECTION
1401 RELAY
OUTPUT 1
1501 AO1
CONTENT
SEL
SYSTEM CONTROL INPUTS
1601 RUN
ENABLE
1604 FAULT
RESET SEL
1606 LOCAL
LOCK
1607 PARAM
SAVE
1608 START
ENABLE 1
1609 START
ENABLE 2
Setting for
Function/Information
fieldbus
control
COMM
Fieldbus reference REF2 is used
COMM+AI
when EXT2 is selected as the active
1
control location. See section
COMM*AI1
Fieldbus references
information on the alternative
settings.
COMM
Enables relay output RO control by
COMM(-1)
signal
0134 COMM RO
135
Directs the contents of the fieldbus
reference
analog output AO.
COMM
Enables the control of the inverted
Run enable signal (Run disable)
through
(RUN_DISABLE); with the ABB
drives profile
(INHIBIT
COMM
Enables fault reset through the
fieldbus
(RESET); with the ABB drives profile
5319 EFB PAR 19
COMM
Local control mode lock signal
through
14 (REQ_LOCALLOC)
DONE
Saves parameter value changes
SAVE...
(including those made through
fieldbus control) to permanent
memory.
COMM
Inverted Start enable 1 (Start
disable) through
WORD 2
COMM
Inverted Start enable 2 (Start
disable) through
WORD 2
Fieldbus control with embedded fieldbus 317
on page
WORD.
0135 COMM VALUE 1
0301 FB CMD WORD 1
5319 EFB PAR 19
OPERATION).
0301 FB CMD WORD 1
bit 7 (RESET).
0301 FB CMD WORD 1
0302 FB CMD
bit 18 (START_DISABLE1)
0302 FB CMD
bit 19 (START_DISABLE2)
Modbus register
address
40003 for REF2
320
for
ABB
DCU
DRV
40134 for signal
0134
40135 for signal
to
0135
ABB
DCU
DRV
40001
40031
bit 3
bit 6
bit 6
bit 3
40001
40031
bit 4
bit 7
bit 4
-
40031
bit
bit 14
41607
-
40032
bit 18
-
40032
bit 19