13 ANALOG INPUTS Analog input signal processing
1301 MINIMUM AI1
-100.0...100.0% Value as a percentage of the full signal range.
Description
When parameter
1201 CONST SPEED SEL
FUNC 1
...
TIMED FUNC
constant speed. 1 = timed function active, 0 = timed
function inactive.
Timed function 1...4 Operation
0
1
When parameter
1201 CONST SPEED SEL
FUN1&2, timed functions 1 and 2 select a constant speed.
1 = timed function active, 0 = timed function inactive.
Timed
Timed
function 1
function 2
0
0
1
0
0
1
1
1
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI1. When used as a
reference, the value corresponds to the reference minimum
setting.
=
0...20 mA
0...100%
=
4...20 mA
20...100%
=
-10...10 mA
-50...50%
Example: If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
parameter
1104 REF1
Note:
MINIMUM AI1
value.
Example: If the minimum value for analog input is 4 mA, the
percentage value for 0...20 mA range is:
(4 mA / 20 mA) · 100% = 20%
Actual signals and parameters 203
4, this timed function selects a
Speed defined by parameter
CONST SPEED 1
Speed defined by parameter
CONST SPEED 2
Operation
Speed defined by parameter
CONST SPEED 1
Speed defined by parameter
CONST SPEED 2
Speed defined by parameter
CONST SPEED 3
Speed defined by parameter
CONST SPEED 4
MIN.
value must not exceed
Def/FbEq
=
TIMED
2
1202
1203
=
TIMED
1202
1203
1204
1205
1.0%
MAXIMUM AI1
1 = 0.1%