Register mapping

The drive parameters, Control/Status word, references and actual values are mapped
to the area 4xxxx so that:
• 40001...40099 are reserved for drive control/status, reference and actual values.
• 40101...49999 are reserved for drive parameters 0101...9999 (eg, 40102 is
parameter 0102). In this mapping, the thousands and hundreds correspond to the
group number, while the tens and ones correspond to the parameter number
within a group.
The register addresses that do not correspond with drive parameters are invalid.
If there is an attempt to read or write invalid addresses, the Modbus interface returns
an exception code to the controller. See
The following table gives information on the contents of the Modbus addresses
40001...40012 and 40031...40034.
Modbus register
40001 Control word
40002 Reference 1
40003 Reference 2
40004 Status word
40005
Actual 1...8
...
40012
40031 Control word LSW
40032 Control word MSW R/W
40033 Status word LSW
Fieldbus control with embedded fieldbus 325
Exception codes
Access Information
R/W
Control word. Supported only by the ABB drives
profile, ie, when
ABB DRV LIM
EFB PAR 19
hexadecimal format.
R/W
External reference REF1. See section
references
R/W
External reference REF2. See section
references
R
Status word. Supported only by the ABB drives profile,
ie, when
5305 EFB CTRL PROFILE
DRV LIM
or
PAR 20
shows a copy of the Control word in
hexadecimal format.
R
Actual value 1...8. Use parameter 5310...
select an actual value to be mapped to Modbus
register 40005...40012.
R/W
0301 FB CMD WORD
of the DCU profile 32-bit Control word.
Supported only by the DCU profile, ie, when
CTRL PROFILE
0302 FB CMD WORD
of the DCU profile 32-bit Control word.
Supported only by the DCU profile, ie, when
CTRL PROFILE
R
0303 FB STS WORD
the DCU profile 32-bit Status word.
Supported only by the DCU profile, ie, when
CTRL PROFILE
on page 327.
5305 EFB CTRL PROFILE
or
ABB DRV
FULL. Parameter
shows a copy of the Control word in
on page 320.
on page 320.
ABB DRV
FULL. Parameter
1, ie, the least significant word
setting is
DCU
PROFILE.
2, ie, the most significant word
setting is
DCU
PROFILE.
1, ie, the least significant word of
setting is
DCU
PROFILE.
setting is
5319
Fieldbus
Fieldbus
setting is
ABB
5320 EFB
5317
to
5305 EFB
5305 EFB
5305 EFB