ABB ACS355 series User Manual page 291

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
8 EVEN 1
8 ODD 1
5305 EFB CTRL
PROFILE
ABB DRV LIM
DCU PROFILE DCU profile
ABB DRV
FULL
5306 EFB OK
MESSAGES
0...65535
5307 EFB CRC
ERRORS
0...65535
5310 EFB PAR 10
0...65535
5311 EFB PAR 11
0...65535
5312 EFB PAR 12
0...65535
5313 EFB PAR 13
0...65535
5314 EFB PAR 14
0...65535
5315 EFB PAR 15
0...65535
5316 EFB PAR 16
0...65535
5317 EFB PAR 17
0...65535
Description
Even parity indication bit, one stop bit, 8 data bits
Odd parity indication bit, one stop bit, 8 data bits
Selects the communication profile. See section
Communication profiles
ABB drives limited profile
ABB drives profile
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
Number of messages
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
Number of messages
Selects an actual value to be mapped to Modbus register
40005.
Parameter index
Selects an actual value to be mapped to Modbus register
40006.
Parameter index
Selects an actual value to be mapped to Modbus register
40007.
Parameter index
Selects an actual value to be mapped to Modbus register
40008.
Parameter index
Selects an actual value to be mapped to Modbus register
40009.
Parameter index
Selects an actual value to be mapped to Modbus register
40010.
Parameter index
Selects an actual value to be mapped to Modbus register
40011.
Parameter index
Selects an actual value to be mapped to Modbus register
40012.
Parameter index
Actual signals and parameters 291
on page 328.
Def/FbEq
2
3
ABB DRV
LIM
0
1
2
0
1 = 1
0
1 = 1
103
1 = 1
104
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1

Hide quick links: