ABB ACS355 series User Manual page 295

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

All parameters
No.
Name/Value
8403 SEQ PROG
PAUSE
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
NOT SEL
DI1
DI2
DI3
DI4
DI5
PAUSED
8404 SEQ PROG
RESET
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
NOT SEL
DI1
DI2
DI3
DI4
DI5
RESET
Description
Selects the source for the Sequence programming pause
signal. When Sequence programming pause is activated, all
timers and outputs (RO/TO/AO) are frozen. Sequence
programming state transition is possible only by parameter
8405 SEQ ST
FORCE.
Pause signal through inverted digital input DI1. 0 = active, 1
= inactive.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
No pause signal
Pause signal through digital input DI1. 1 = active, 0 =
inactive.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Sequence programming pause enabled
Selects the source for the Sequence programming reset
signal. Sequence programming state
STATE) is set to the first state and all timers and outputs
(RO/TO/AO) are set to zero.
Reset is possible only when Sequence programming is
stopped.
Reset through inverted digital input DI1. 0 = active, 1 =
inactive.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
No reset signal
Reset through digital input DI1. 1 = active, 0 = inactive.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Reset. After reset parameter value is automatically set to
NOT
SEL.
Actual signals and parameters 295
(0168 SEQ PROG
Def/FbEq
NOT SEL
-1
-2
-3
-4
-5
0
1
2
3
4
5
6
NOT SEL
-1
-2
-3
-4
-5
0
1
2
3
4
5
6