190 Actual signals and parameters
Actual signals
No.
Name/Value
0406 VOLTAGE AT
FLT
0407 CURRENT AT
FLT
0408 TORQUE AT
FLT
0409 STATUS AT
FLT
0412 PREVIOUS
FAULT 1
0413 PREVIOUS
FAULT 2
0414 DI 1-5 AT FLT
Description
Intermediate circuit voltage in V DC at the time the latest
fault occurred
Motor current in A at the time the latest fault occurred
Motor torque as a percentage of the motor nominal torque
at the time the latest fault occurred
Drive status in hexadecimal format at the time the latest
fault occurred
Fault code of the 2nd latest fault. See chapter
on page
349
for the codes.
Fault code of the 3rd latest fault. See chapter
on page
349
for the codes.
Status of digital inputs DI1...5 at the time the latest fault
occurred.
Example (panel):
• 10000 = DI1 is on, DI2...DI5 are off.
• 10010 = DI1 and DI4 are on, DI2, DI3 and DI5 are off.
Example (DWL2):
• 16 (decimal) = DI1 is on, DI2...DI5 are off.
• 18 (decimal) = DI1 and DI4 are on, DI2, DI3 and DI5 are
off.
FbEq
1 = 0.1 V
1 = 0.1 A
1 = 0.1%
Fault tracing
1 = 1
Fault tracing