ABB ACS355 series User Manual page 362

Hide thumbs Also See for ACS355 series:
Table of Contents

Advertisement

362 Fault tracing
CODE FAULT
0022
SUPPLY PHASE
(3130)
0306
bit 5
(programmable
fault function
3016)
0023
ENCODER ERR
(7301)
0306
bit 6
(programmable
fault function
5003)
0024
OVERSPEED
(7310)
0306
bit 7
0027
CONFIG FILE
(630F)
0306
bit 10
0028
SERIAL 1 ERR
(7510)
0306
bit 11
(programmable
fault function
3018, 3019)
0029
EFB CON FILE
(6306)
0306
bit 12
CAUSE
Intermediate circuit DC
voltage is oscillating due
to missing input power
line phase or blown fuse.
Trip occurs when DC
voltage ripple exceeds
14% of nominal DC
voltage.
Communication fault
between pulse encoder
and pulse encoder
interface module or
between module and
drive.
Motor is turning faster
than 120% of the highest
allowed speed due to
incorrectly set
minimum/maximum
speed, insufficient
braking torque or
changes in load when
using torque reference.
Operating range limits
are set by parameters
2001 MINIMUM SPEED
and
2002 MAXIMUM
SPEED
(in vector
control) or
2007
MINIMUM FREQ
and
2008 MAXIMUM FREQ
(in scalar control).
Internal configuration file
error
Fieldbus communication
break
Configuration file reading
error
WHAT TO DO
Check input power line fuses and
installation.
Check for input power supply
imbalance.
Check the load.
Check fault function parameter
DC
STABILIZER.
Check pulse encoder and its wiring,
pulse encoder interface module and
its wiring and parameter group
ENCODER
settings.
Check minimum/maximum frequency
settings (parameters
SPEED
and
2002 MAXIMUM
SPEED).
Check adequacy of motor braking
torque.
Check applicability of torque control.
Check need for brake chopper and
resistor(s).
Replace the drive.
Check status of fieldbus
communication. See chapter
control with embedded fieldbus
page 313, chapter
Fieldbus control
with fieldbus adapter
appropriate fieldbus adapter manual.
Check fault function parameter
COMM FAULT FUNC
COMM FAULT TIME
Check connections and/or noise on
the line.
Check if master can communicate.
Error in reading the configuration files
of the embedded fieldbus. See
fieldbus user's manual.
2619
50
2001 MINIMUM
Fieldbus
on
on page
339
or
3018
and
3019
settings.