1 Alarms
Definitions:
Reactions:
Remedy:
Program Continuation:
17130
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
17140
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
17150
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
1-256
An attempt has been made by means of the system variable $A_INA[n] to read an analog
input n that has not been activated by the MD 10300 FASTIO_ANA_NUM_INPUTS.
- Alarm display.
- Interface signals are set.
- Correction block is reorganized.
Please inform the authorized personnel/service department. Modify part program or
machine data accordingly.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 analog output no. %3 not activated
%1 = Channel number
%2 = Block number, label
%3 = No. of output
An attempt has been made by means of the system variable $A_OUTA[n] to write or read
an analog output n that has not been activated by the MD 10310
FASTIO_ANA_NUM_OUTPUTS.
- Alarm display.
- Interface signals are set.
- Correction block is reorganized.
Please inform the authorized personnel/service department. Modify part program or
machine data accordingly.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 NCK output %3 is assigned to a function via machine data
%1 = Channel number
%2 = Block number, label
%3 = No. of output
The programmed digital/analog output is assigned to an NC function (e.g. software
cams).
- Alarm display.
- Interface signals are set.
- Correction block is reorganized.
Please inform the authorized personnel/service department. Use another output or deacti-
vate concurrent NC function via MD.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 maximum of %3 NCK outputs programmable in the block
%1 = Channel number
%2 = Block number, label
%3 = Quantity
No more than the specified number of outputs may be programmed in an NC block.
The quantity of hardware outputs is defined in the MDs:
10360 FASTIO_DIG_NUM_OUTPUTS and
10310 FASTIO_ANA_NUM_OUTPUTS
- Alarm display.
- Interface signals are set.
- Correction block is reorganized.
Program fewer digital/analog outputs in a block. The specified maximum number applies
in each case separately for analog or digital outputs. If necessary, program two NC
blocks.
Clear alarm with NC START or RESET key and continue the program.
SINUMERIK 840D/840Di/810D Diagnostics Guide (DA) – 11.02 Edition
Siemens AG, 2002. All rights reserved
11.02