Installing An Rpdu; Installing The Rpdu Horizontally - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Step 4 Push the battery back onto the guide rails, and secure the battery pack to the cabinet rack rails
using mounting ears and screws, as shown in
Figure 2-26 Installing a battery pack
Step 5 Install other battery packs from bottom to top in the same way.
----End

2.2.6 Installing an rPDU

2.2.6.1 Installing the rPDU Horizontally

Context
Procedure
Step 1 Open the cabinet rear door, and install four floating nuts at the position where the rPDU is to
be installed.
Step 2 Secure the rPDU.
Issue 07 (2019-12-20)
Putting the guide rail between the notches on the rack rail facilitates locating the installation position.
If the Converged Cabinet is configured with an rPDU that needs to be horizontally
installed, install the rPDU onsite.
For the 42 U Converged Cabinet, install the rPDU at the 31 U position on the cabinet
rear door.
For the 24 U Converged Cabinet, install the rPDU at the 16 U position on the cabinet
rear door.
Adjust the position for installing the rPDU based on site requirements.
Copyright © Huawei Technologies Co., Ltd.
Figure
2-26.
2 Installation
45