Huawei FusionModule500 User Manual page 162

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Alarm
Rectifier
fault
(Reason
5)
Rectifier
fault
(Reason
6)
Rectifier
fault
(Reason
7)
Rectifier
fault
(Reason
9)
Rectifier
fault
(Reason
10)
Rectifier
alarm
(Reason
1)
Rectifier
alarm
(Reason
2)
Rectifier
alarm
(Reason
3)
Internal
fault
(Reason
1)
Internal
fault
(Reason
2)
Issue 07 (2019-12-20)
Severity
Possible Cause
Critical
The hardware is damaged.
Critical
1. The ambient temperature
Critical
exceeds 40° C.
2. The air channel is blocked.
3. The fan is abnormal.
Critical
The rectifier is faulty.
Critical
The digital signal processing
(DSP) or complex
programmable logical device
(CPLD) chip is faulty.
Minor
The EEPROM chip is faulty.
Minor
The single-side bus capacitor
is faulty.
Minor
The bus capacitor is faulty.
Critical
The auxiliary power source is
faulty.
Critical
The soft-start resistor is
damaged.
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance
Solution
Contact Huawei technical
support for repair.
1. Decrease the ambient
temperature.
2. Keep the air intake and
exhaust vents of the UPS
unobstructed.
3. Clean up foreign matter
around the fan. If the alarm
persists, contact Huawei
technical support.
Contact Huawei technical
support for repair.
Contact Huawei technical
support for repair.
Contact Huawei technical
support for repair.
Contact Huawei technical
support for repair.
Contact Huawei technical
support for repair.
Contact Huawei technical
support for repair.
Contact Huawei technical
support for repair.
153

Advertisement

Table of Contents
loading

Table of Contents