Step 3 Install a new smoke sensor and reconnect the cables.
Step 4 Install the spare smoke detector in the original position.
----End
Follow-up Procedure
Check whether the new smoke sensor works properly. If its status is displayed on the WebUI
of the ECC800e, the new smoke sensor works properly.
4.5.4 (Optional) Replacing a Fan Assembly
Context
For a customized FusionModule500, replace a fan assembly by performing the operations in
this section if a fan assembly is installed at the top of the cabinet.
Preparations
Tools: Phillips screwdriver, flat-head screwdriver
Material: spare fan assembly
Procedure
Step 1 Open the cabinet rear door.
Step 2 Turn off the fan assembly switch to disconnect power from the fan assembly, as shown in
Figure
Step 3 Disconnect the power cable from the rPDU.
Step 4 Remove the faulty fan assembly from the cabinet.
Issue 07 (2019-12-20)
4-25.
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance
198