Commissioning A T/H Sensor - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)

3.2.6.4 Commissioning a T/H Sensor

Procedure
Step 1 (Optional) Add the T/H sensor to the ECC800.
1.
2.
3.
4.
5.
Step 2 Check functions of the T/H sensor.
Table 3-8 Function commissioning
Check Method
The temperature and
humidity in the
equipment room
exceeds the T/H
alarm threshold.
Set T/H sensor
alarm thresholds.
----End
Issue 07 (2019-12-20)
In the multi-cabinet scenario, this operation should be performed for the T/H sensor on the network
cabinet.
On the WebUI, choose System Settings > Equipment Management.
(Optional) Connected to the ECC800e scenario: Set Device type to T/H Sensor,
Connect to to ECC800e, Communications port to COM3, and Device Address to 2.
(Optional) Connected to the independent deployment AI/DI module: Set Device type to
T/H Sensor, Connect to to Independent Deployment AI_DI Unit, Communications
port to COM_OUT, and Device Address to 2.
Click Connect Test.
If the message "Succeeded to connect" is displayed, go to the next step. Otherwise, reset
the parameters.
Click Add Device.
Normal Connection Status
A T/H alarm is displayed on the active alarm page of the app or
WebUI.
Choose Monitoring > Aisle > T/H Sensor Group > T/H Sensor
n > Running Parameters and set High Temperature Alarm
Threshold, Low Temperature Alarm Threshold, High
Humidity Alarm Threshold, and Low Humidity Alarm
Threshold as required.
NOTE
Copyright © Huawei Technologies Co., Ltd.
The default values of High Temperature Alarm Threshold, Low
Temperature Alarm Threshold, High Humidity Alarm Threshold, and
Low Humidity Alarm Threshold are 30.0° C, 5.0° C, 85% RH, and 15%
RH, respectively. You can change the values based on site requirements.
You are advised to raise or lower the temperature alarm threshold 3–5° C
based on the ambient temperature.
You are advised to raise or lower the humidity alarm threshold
10%–30% RH based on the ambient humidity.
3 Commissioning Guide
109