Huawei FusionModule500 User Manual page 137

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Maintenance area
UPS
Battery
Issue 07 (2019-12-20)
Item
Transformer fan
Operating
environment
Liquid crystal
display (LCD)
Battery management
alarm
Battery appearance
Copyright © Huawei Technologies Co., Ltd.
Operation
Check whether
abnormal noise is
generated when the
transformer fan is
rotating.
N/A
N/A
N/A
N/A
Expected
Troubleshooting
Result
The transformer
4.5.2.4 Replacing
fan rotates
the Transformer Fan
normally without
Fuse
abnormal noise.
Ambient
If the humidity and
temperature:
temperature are
0–40° C
abnormal, check the
smart cooling
Humidity:
product status.
5–95% RH
(non-condensi
ng)
According to the
If an alarm is
status icons on
present, rectify the
the LCD, all
fault by checking
units are
the device status
operating
and parameters.
properly. No
fault or alarm
information is
found in the
active and
historical alarm
records.
No battery
Identify the cause of
management
an alarm based on
alarm is
the alarm
generated.
information.
The surface is
If the battery
clean and tidy
appearance is
without
abnormal, contact
stains.
Huawei technical
support.
The battery
terminals are
intact.
Batteries are
free from
damage and
cracks.
Batteries are
free from acid
leakage.
Batteries are
not deformed
or bulged.
4 Maintenance
OFF, switch it
on.
128