FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Maintenance area
UPS
Battery
Issue 07 (2019-12-20)
Item
loop after power-off
Operating
environment
Liquid crystal
display (LCD)
Cleanliness
Parameter
configuration
Power cables and
terminals (between
the UPS and the
power distribution
subrack)
Battery management
alarm
Battery appearance
Copyright © Huawei Technologies Co., Ltd.
Operation
using an insulation
tester.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Expected Result Troubleshooting
greater than or
poor, check and
equal to 2
maintain the signal
megohms.
cable, emergency
fan, and smart ETH
gateway.
Ambient
If the humidity and
temperature:
temperature are
0–40° C
abnormal, check the
smart cooling
Humidity:
product status.
5–95% RH
(non-condensi
ng)
According to the
If an alarm is
status icons on
present, rectify the
the LCD, all units
fault by checking
are operating
the device status
properly. No fault
and parameters.
or alarm
information is
found in the
active and
historical alarm
records.
Wipe the cabinet
Remove the dust,
surface using a
especially from the
white paper and
front panel.
the paper does not
turn black.
The configuration
Reset the
of the output
parameters.
voltage grade,
frequency,
number of
batteries, and
battery capacity
meets
requirements.
The insulation
layer of cables is
intact and
terminals are free
from signs of
ignition.
No battery
Identify the cause of
management
an alarm based on
alarm is
the alarm
generated.
information.
1. The surface is
If the battery
4 Maintenance
Replace the
cables.
Secure output
terminals.
139