Huawei FusionModule500 User Manual page 140

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Maintenance area
Camera
The Intelligent
Battery Monitoring
System
The Water Sensor
Issue 07 (2019-12-20)
Item
Cable connections
Camera availability
Battery management
alarm
Cleanliness
Battery connection
Ambient temperature
of the intelligent
battery monitoring
system
Functions of the
water sensor
Copyright © Huawei Technologies Co., Ltd.
Operation
N/A
N/A
On the camera
WebUI, choose
Playback, and
specify values Start
time, End time,
and Record type
for the camera to be
queried. Then, click
Query and you can
view the video in
real time.
N/A
N/A
N/A
N/A
Immerse the water
sensor into the
water and check
whether a water
leakage alarm is
generated by the
water sensor.
Expected
Troubleshooting
Result
The cable
Secure loose cables.
connections are
secure.
Cables are not
Replace damaged
damaged.
cables.
The video is
If the monitoring
displayed
video is not
normally.
displayed, check
that the IP address is
correctly set, and
check cable
connection or
replace the camera.
For details, see
4.5.3.4 Replacing a
Camera.
No battery
Find the cause of an
management
alarm based on the
alarm is
alarm information.
generated.
Wipe the battery
Remove dust from
surface using a
the battery surface.
piece of white
paper and the
paper does not
turn black.
Battery terminals
Ensure that battery
and cables are in
terminals and cables
good contact.
are in good contact.
The ambient
Find the cause of an
temperature of
abnormal
the intelligent
temperature.
battery
monitoring
system is lower
than 45° C.
When the water
If there is no alarm,
sensor comes
replace the water
into contact with
sensor.
water, a water
leakage alarm is
generated.
4 Maintenance