Huawei FusionModule500 User Manual page 164

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Alarm
ble ver.
(Reason
4)
Incompati
ble ver.
(Reason
5)
Incompati
ble ver.
(Reason
6)
Charger
alarm
(Reason
3)
Charger
alarm
(Reason
4)
Charger
alarm
(Reason
6)
Charger
alarm
(Reason
7)
Charger
alarm
(Reason
8)
Charger
alarm
(Reason
9)
Charger
alarm
(Reason
10)
OL
timeout
(Reason
1)
OL
Issue 07 (2019-12-20)
Severity
Possible Cause
Critical
Critical
Critical
The charger capacitor is faulty.
Critical
The charger output is
short-circuited.
Critical
The charger is faulty.
Critical
Critical
Critical
Critical
The load exceeds the rated
Critical
inverter loading capacity.
Critical
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance
Solution
Contact Huawei technical
support for repair.
Rectify battery port short
circuits. After you clear the
alarm, restart the UPS. If the
alarm persists, contact Huawei
technical support for repair.
Contact Huawei technical
support for repair.
Reduce the load or replace the
UPS with a large-capacity
UPS.
155