Maintenance area
ECC800e
Issue 07 (2019-12-20)
Item
Shallow discharge
test (recommended)
AC input
Operating
environment
Monitoring module
indicator
Copyright © Huawei Technologies Co., Ltd.
Operation
N/A
N/A
N/A
N/A
Expected Result Troubleshooting
V/cell ± 0.02
V/cell.
Float charging
voltage: 2.25
2. If the charging
V/cell ± 0.02
V/cell.
3. If the fault
1. Locate the cause
Conduct a
shallow discharge
test when the
UPS is backed up
to verify that the
2. If the fault
batteries can
discharge
normally.
Input voltage:
If the input voltage
100–240 V AC
is abnormal, check
the power grid and
Frequency: 50
input cable
Hz/60 Hz
connection.
Ambient
If the humidity or
temperature:
temperature is
–20° C to
abnormal, check the
+65° C
smart cooling
product status.
Humidity:
5–95% RH
(non-condensi
ng)
The monitoring
If the indicator is
module indicator
off or any abnormal
is steady green or
condition occurs,
4 Maintenance
and float
charging voltage
of a battery are
normal.
voltage of a
battery exceeds
the
specifications
requirement,
perform a
complete
forcible
equalized
charging for the
battery, and
check again
whether the
voltage is
normal.
persists, contact
Huawei
technical
support.
when an
exception is
identified.
persists, contact
Huawei
technical
support.
135