FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Figure 3-1 Circuit breakers
(1) Maintenance bypass circuit breaker
(3) UPS output circuit breaker
(5) SPD circuit breaker
Procedure
Step 1 Switch on all SPD circuit breakers.
Step 2 Switch on the power input circuit breaker outside the cabinet to power on the cabinet.
Step 3 Close the UPS input switch.
Step 4 After UPS startup, set the language (default: English), system parameters, and battery
parameters, and start the inverter, and then close the UPS output switch.
Table 3-1 Battery parameters
Parameter
Batteries (3 kVA/6
Issue 07 (2019-12-20)
If the surge protection module indicator is green, the SPD is running properly. If the surge protection
module indicator is red, the surge protection module is faulty and must be replaced immediately.
To set the number of batteries and battery capacity, choose Settings > Battery Parameters > Basic. To
set the maximum current, choose Settings > Battery Parameters > Equalized Change.
Copyright © Huawei Technologies Co., Ltd.
Default Value
20
3 Commissioning Guide
(2) UPS input circuit breaker
(4) Branch switch
(6) SPD
Setting Value
Set as required