7 ADDRESSABLE PARAMETERS

7.1 COMMANDER 100/V100 – Coils
Coil No.
Variable Label
01
Process Variable Fail State
02
Remote Set Point Fail State
03
A/D Converter Fail State
06
Alarm State 1
07
Alarm Indicator 1
08
Alarm State 2
09
Alarm Indicator 2
14
Digital Input State
15
Digital Output State
16
Relay 1 State
17
Relay 2 State
19
On/Off Output 1 (Heat)
20
On/Off Output 2 (Cool)
30
Auto/Manual State
31
Control Action
32
Select Local Set Point
33
Select Remote Set Point
34
Select Fixed Set Point 1
35
Select Fixed Set Point 2
36
Select Fixed Set Point 3
37
Select Fixed Set Point 4
7.2 COMMANDER 100/V100 – Registers

7.2.1 Analog Inputs

Register
Variable Label
2
Process Variable Input
3
PV Decimal Places
5
Remote Set Point Input
6
Remote SP Decimal Places
16
Read/Write Limits/Values
R
1 = Failed
R
1 = Failed
R
1 = Failed
R
1 = Active
R
1 = On
R
1 = Active
R
1 = On
R
1 = On
R
1 = On
R
1 = On
R
1 = On
R
1 = On
R
1 = On
RW
0 = Auto; 1 = Manual
W
0 = Reverse; 1 = Direct
W
1 = Local
W
1 = Remote
W
1 = Selected
W
1 = Selected
W
1 = Selected
W
1 = Selected
Read/Write Limits/Values
R
–999 to 9999
R
0 to 4
R
–999 to 9999
R
0 to 2