Bico: De-Activated Interconnections Present; Inserted Component Not Initialized; Topology: Drive Object Number Does Not Exist In Configuration - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

SINAMICS alarms
201318
<location>BICO: De-activated interconnections present
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
This alarm is used in the following cases:
- If an inactive/non-operational drive object is active again/ready for operation
- If there are items in the list of BI/CI parameters (r9498[0...29], r9499[0...29])
- If the BICO interconnections saved in the list of BI/CI parameters (r9498[0...29], r9499[0...29]) have actually been
changed
Remedy:
Reset alarm:
- Set p9496 to 1 or 2
or
- de-activate the drive object again.
201319
<location>Inserted component not initialized
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, CU_LINK, HUB, SERVO_COMBI, SERVO_SINUMERIK828,
SIC_COMBI, SIC_SINUMERIK_828, TM120, TM54F_MA, TM54F_SL
Reaction:
NONE
Acknowledge:
NONE
Cause:
Initialization is required for at least one inserted component.
This is only possible if the pulses are inhibited for all the drive objects.
Remedy:
Activate pulse inhibit for all drive objects.
201320
<location>Topology: Drive object number does not exist in configuration
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A drive object number is missing in p0978
Alarm value (r2124, interpret decimal):
Index of p0101 under which the missing drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
532
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinumerik 828d

Table of Contents