NCK alarms
Remedy:
Set axis/spindle disable of the master axis
Program
Clear alarm with the RESET key. Restart part program
Continuation:
16954
[Channel %1: ] Block %2 programmed stop prohibited in stop delay area
Parameters:
%1 = Channel ID
%2 = Block number, label
Definitions:
In a program area (stop delay area) that is bracketed with DELAYFSTON and DELAYFSTOF, a program command
was used that causes a stop. No commands other than G4 are permissible that might cause a stop even though only
shortly. A stop delay area can also be defined by MD11550 $MN_STOP_MODE_MASK.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
MD11550 $MN_STOP_MODE_MASK and language command DELAYFSTON DELAYFSTOF
Program
Clear alarm with the RESET key. Restart part program
Continuation:
16955
[Channel %1: ] Stop in stop delay area is delayed
Parameters:
%1 = Channel ID
Definitions:
In a program area (stop delay area) that is bracketed by DELAYFSTON and DELAYFSTOF, an event has been
detected that causes a stop. The stop is delayed and executed after DELAYFSTOF. A stop delay area can also be
defined by MD11550 $MN_STOP_MODE_MASK.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
MD11550 $MN_STOP_MODE_MASK and language command DELAYFSTON DELAYFSTOF
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
16956
[Channel %1: ] Program %2 cannot be started due to global start disable.
Parameters:
%1 = Channel ID
%2 = String (path with program name)
Definitions:
The program selected in this channel cannot be started as "Global start disable" had been set.
Note:
PI "_N_STRTLK" sets the "Global start disable" and PI "_N_STRTUL"
deletes the "Global start disable".
The alarm is switched on with MD11411 $MN_ENABLE_ALARM_MASK bit 6.
Reaction:
Alarm display.
Remedy:
Delete the "Global start disable" and restart.
Program
Clear alarm with the Delete key or NC START.
Continuation:
262
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0