61013
[Channel %1: ] Block %2: Basic settings were changed, program cannot be executed
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
The basic settings are not compatible with the generated program. Alarm triggered by following cycles: E_CP_CE,
E_CP_CO, E_CP_DR, F_CP_CE, F_CP_CO, F_CP_DR.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Check and, if necessary, change the basic settings.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
61014
[Channel %1: ] Block %2: Return plane exceeded
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Alarm triggered by following cycles: CYCLE72.
Remedy:
Check parameter RTP.
61015
[Channel %1: ] Block %2: Contour is not defined
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Alarm triggered by following cycles: .
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Program
Clear alarm with the RESET key. Restart part program
Continuation:
61016
[Channel %1: ] Block %2: System frame for cycles missing
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
All measuring cycles can trigger this alarm.
Remedy:
Set MD 28082: MM_SYSTEM_FRAME_MASK, Bit 5=1.
61017
%[[Channel %1: ] Block %2: %]function %4 not present in NCK
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Alarm triggered by following cycles: .
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
NCK alarms