Overview of Alarms
SINAMICS-Alarms
Remedy:
None necessary. The alarm automatically disappears when the limit value is undershot.
See also: p0290 (Power unit overload response)
205050
<location>Parallel circuit: Pulse enable in spite of pulse inhibit
Message
%1
value:
Drive object:
A_INF, B_INF, S_INF, VECTOR
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
VECTOR: OFF2 (NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
A power unit signals that the pulses are enabled although the pulses are inhibited.
Fault value (r0949, interpret decimal):
Number of the power unit involved.
Remedy:
The power unit is defective and must be replaced.
205051
<location>Parallel circuit: Power unit pulse enable missing
Message
%1
value:
Drive object:
A_INF, B_INF, S_INF, VECTOR
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
VECTOR: OFF2 (NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
For one or several power units, the pulses were not able to be enabled.
Fault value (r0949, interpret decimal):
Number of the power unit involved.
Remedy:
- acknowledge power unit faults that are still present.
- inhibit the pulses of the power unit involved (p7001).
205052
<location>Parallel circuit: Illegal current dissymmetry
Message
%1
value:
Drive object:
A_INF, B_INF, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The deviation of the individual currents of the power units exceeds the alarm threshold specified in
p7010.
Alarm value (r2124, interpret decimal):
1: Phase U.
2: Phase V.
3: Phase W.
Remedy:
- inhibit the pulses of the faulted power unit (p7001).
- check the connecting cables. Loose contacts can cause current spikes.
- the motor reactors are non-symmetrical or faulty and must be replaced.
- the CTs must be calibrated or replaced.
205053
<location>Parallel circuit: Inadmissible DC link voltage dissymmetry
Message
-
value:
Drive object:
A_INF, B_INF, S_INF, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The deviation of the DC link voltage measured values exceeds the alarm threshold specified in p7011.
Remedy:
- inhibit the pulses of the faulted power unit (p7001).
- check the DC link connecting cables.
- the DC link voltage measurement is incorrect and must be calibrated or renewed.
2-720
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009