03/2009
xx = 14 hex:
The length of the receive telegram does not match the receive list and the receive telegram is too
early.
xx = 04 hex:
The length of the receive telegram does not match the receive list.
xx = 15 hex:
The type of the receive telegram does not match the receive list and the receive telegram is too early.
xx = 05 hex:
The type of the receive telegram does not match the receive list.
xx = 16 hex:
The address of the power unit in the telegram and in the receive list does not match and the receive
telegram is too early.
xx = 06 hex:
The address of the power unit in the telegram and in the receive list do not match.
xx = 19 hex:
The error bit in the receive telegram is set and the receive telegram is too early.
xx = 09 hex:
The error bit in the receive telegram is set.
xx = 10 hex:
The receive telegram is too early.
Remedy:
- carry out a POWER ON.
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
240885
<location>CX32 DRIVE-CLiQ (CU): Cyclic data transfer error
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred from the controller extension involved to the Con-
trol Unit.
The nodes do not send and receive in synchronism.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 1A hex:
Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
xx = 21 hex:
The cyclic telegram has not been received.
xx = 22 hex:
Timeout in the telegram receive list.
xx = 40 hex:
Timeout in the telegram send list.
xx = 62 hex:
Error at the transition to cyclic operation.
Remedy:
- check the power supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
240886
<location>CX32 DRIVE-CLiQ (CU): Error when sending DRIVE-CLiQ data
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY